IEC Electrical | 1000 | |||||
Nominal AC Voltage Uo/ Un | 1000 V | |||||
Maximum Continuous Operating Voltage (DC) Uc | 1000 V | |||||
Nominal Discharge Current (8/20 μs) In | 20 kA | |||||
Maximum Discharge Current (8/20 μs) Imax | 40 kA | |||||
Impulse Discharge Current (10/350 μs) Iimp | 6.25 kA | |||||
Voltage Protection Level | Up | 3.6 kV | ||||
Response Time | tA | < 25 ns | ||||
Back-Up Fuse (max) | 125 A gL / gG | |||||
Short-Circuit Current Rating (AC) ISCCR | 25 kA / 50 kA | |||||
Mechanical & Environmental | ||||||
Operating Temperature Range | Ta | -40ºF to +158ºF [-40ºC to +70ºC] | ||||
Permissible Operating Humidity | RH | 5%...95% | ||||
Atmospheric pressure and altitude | 80k Pa ... 106k Pa / -500 m.....2000 m | |||||
Terminal Screw Torque | Mmax | 39.9 Ibf ·in [4.5 Nm] | ||||
Conductor Cross Section (max) | 2 AWG (Solid, Stranded) / 4 AWG (Flexible) | |||||
35 mm2 (Solid, Stranded) / 25 mm2(Flexible) | ||||||
Mounting | 35 mm DIN Rail, EN 60715 | |||||
Degree of Protection | IP 20 (built-in) | |||||
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | |||||
Thermal Protection | Yes | |||||
Operating State / Fault Indication | Green ok / Red defect | |||||
Remote Contacts (RC)RC Switching CapacityRC Conductor Cross Section (max) | OptionalAC: 250V / 0.5 A; DC: 250V / 0.1 A;125V / 0.2 A;75V / 0.5 A16 AWG (Solid) / 1.5 mm2(Solid) |