LY-C40PV 3S Surge Protection Device

Protect your electronic devices with the LY-C40PV 3S Surge Protection Device. Manufactured in our factory for reliable quality and performance.

Request a Quote
  • LY-C40PV 3S Surge Protection Device
  • LY-C40PV 3S Surge Protection Device

PRODUCTS DETAILS

Type
SPD according to EN 61643-31 / IEC 61643-31

type 1+2 / class I+II

Max. continuous operating DC voltage (DC+)-PE,(DC-)-PE  ,(DC+)-(DC-)  Ucpv

1500 V DC

Nominal discharge current (8/20μs) In

20 kA

Maximum discharge current (8/20μs) Imax

40 kA

Maximum impulse current (8/20μs) Itotal

40 kA

Maximum impulse current (10/350μs) Iimp

6.25 kA

Maximum impulse current (10/350μs) Itotal

12.5 kA

continuous current for PV application ICPV

0.2 mA

Voltage protection level (DC+)-PE,(DC-)-PE  (DC+)-(DC-) Up 

5.0 kV

Response time tA

25 ns (L-N)

Short-Circuit Current Rating Iscpv

2000 A

Residual current a.c. and d.c.           IPE

0.3 mA(DC), 0.3 mA(AC),

Humidity range

5% ... 95%

Range of operating temperatures TU

-40°C ... +70°C

Atmospheric pressure and altitude

80k Pa ... 106k Pa, -500 m ... 2000 m

Operating state / fault indication

Green ok / Red defect

Number of ports

One port

Cross-sectional area (max.) 

2 AWG (Solid, Stranded) / 4 AWG (Flexible)

35 mm2 (Solid, Stranded) / 25 mm2 (Flexible)

For mounting on

35 mm DIN rail acc. to EN 60715

Enclosure material

thermoplastic

Place of installation

indoor installation

Degree of protection

IP 20

Capacity

4 module(s), DIN 43880

Approvals

-

Type of remote signalling contact

changeover contact

a.c. switching capacity

250V / 0.5 A

d.c. switching capacity

250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A

Cross-sectional area for remote signalling terminals

max. 1.5 mm2 solid / flexible

Remote signalling alarming mode

Normal: closed; failure: open-circuit

Acessibility

Inaccessible

Protection fuction

Overcurrent

PV earthing system

Earthed and Unearthed (both)

SPD failure mode (OCFM/SCFM)

OCFM

This product can only be installed and maintained by qualified professionals. The installation position cannot be touched by hands. Ensure that it is unpowered and check whether the SPD is all right before installation. If there’s damage or the display window is red, the SPD cannot be used any more; if the window is green, the SPD is normal. The installation of SPD should be based on Fig. 3 IEC 60364-5-53. The cross-sectional area of ground wire should not be less than 4 mm2, and the length of total lead not more than 0.5m. The minimum distance from any earthed conductive surface at which the SPD can be installed is 8mm. Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (NC, COM and NO, normally closed), applicable for remote centralized monitoring or alarm. After the connection, check if the module is fitted in. If so, NC and COM are closed; if not, repress the module.

Hot Products

LY1-D20M/1(S)+1 Pluggable Single-Pole SPD

LY1-D20M/1(S)+1 Pluggable Single-Pole SPD

LY-ZFC Intelligent lightning detection module

LY-ZFC Intelligent lightning detection module

LYSCB SPD back-up protector

LYSCB SPD back-up protector

PRODUCT DATASHEET LY1-C40 AC Surge protective device

PRODUCT DATASHEET LY1-C40 AC Surge protective device

Ly-j, 3m Lightning Counter Surge Protection Device

Ly-j, 3m Lightning Counter Surge Protection Device

LY-C40PV 3S Surge Protection Device

LY-C40PV 3S Surge Protection Device

LY1-C40PV/2(S) 1000V Pluggable Single-Pole SPD

LY1-C40PV/2(S) 1000V Pluggable Single-Pole SPD

LY1-C40 Surge Protection Device

LY1-C40 Surge Protection Device

LY21-1 RJ11 telephone surge protective device

LY21-1 RJ11 telephone surge protective device

Ly Varistor Surge Protection Device

Ly Varistor Surge Protection Device

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours